NEC 705.12(B) — the 120% busbar rule
The most-cited residential solar interconnection rule. NEC 705.12(B) (the "120% rule") limits a load-side (back-fed breaker) connection so the busbar isn't overloaded: busbar rating × 1.2 ≥ main breaker + sum of back-fed solar breakers.
The 120% allowance by panel
| Busbar | Main breaker | 120% allowance | Max back-fed solar OCPD | Result |
|---|---|---|---|---|
| 100 A | 100 A | 120 A | 20 A | ✓ within 120% |
| 125 A | 125 A | 150 A | 25 A | ✓ within 120% |
| 200 A | 150 A | 240 A | 90 A | ✓ within 120% |
| 200 A | 200 A | 240 A | 40 A | ✓ within 120% |
| 225 A | 200 A | 270 A | 70 A | ✓ within 120% |
When the 120% rule doesn't fit
If no legal main-breaker size fits the busbar, the code-compliant alternatives are a supply-side (line-side) tap per 705.11 (ahead of the service disconnect, so the busbar isn't back-fed), a main-breaker derate, or a line-side/feed-through connection. Solar Scripto flags the 120% result live and proposes the legal remedy.
Related: 690.8 conductor & OCPD · 240.6 breaker sizes.