NEC 705.12(B) — the 120% busbar rule

The most-cited residential solar interconnection rule. NEC 705.12(B) (the "120% rule") limits a load-side (back-fed breaker) connection so the busbar isn't overloaded: busbar rating × 1.2 ≥ main breaker + sum of back-fed solar breakers.

The 120% allowance by panel

BusbarMain breaker120% allowanceMax back-fed solar OCPDResult
100 A100 A120 A20 A✓ within 120%
125 A125 A150 A25 A✓ within 120%
200 A150 A240 A90 A✓ within 120%
200 A200 A240 A40 A✓ within 120%
225 A200 A270 A70 A✓ within 120%
Example: a 200 A busbar allows 240 A total. With a 150 A main you may back-feed up to 90 A of solar; with a 200 A main only 40 A, so a main-breaker derate or a supply-side (line-side) tap under 705.11 is often needed.

When the 120% rule doesn't fit

If no legal main-breaker size fits the busbar, the code-compliant alternatives are a supply-side (line-side) tap per 705.11 (ahead of the service disconnect, so the busbar isn't back-fed), a main-breaker derate, or a line-side/feed-through connection. Solar Scripto flags the 120% result live and proposes the legal remedy.

Related: 690.8 conductor & OCPD · 240.6 breaker sizes.