NEC 250.122 equipment grounding conductor sizing

The NEC Table 250.122 minimum size of equipment grounding conductors, sized by the rating of the overcurrent device ahead of the circuit. Copper shown; aluminum upsizes.

Table 250.122 — EGC by OCPD rating (copper)

OCPD ratingCopper EGCEngine result
≤ 15 A14 AWG14 AWG
≤ 20 A12 AWG12 AWG
≤ 60 A10 AWG10 AWG
≤ 100 A8 AWG8 AWG
≤ 200 A6 AWG6 AWG
≤ 300 A4 AWG4 AWG
≤ 400 A3 AWG3 AWG
≤ 500 A2 AWG2 AWG
≤ 600 A1 AWG1 AWG
≤ 800 A1/01/0
≤ 1000 A2/02/0
≤ 1200 A3/03/0
The EGC is sized from the OCPD rating, not the circuit conductor — but per 250.122(A) it never has to be larger than the circuit conductors. When phase conductors are upsized for voltage drop, the EGC is upsized proportionally (250.122(B)).

Related: 250.66 grounding electrode conductor · 240.6 OCPD sizes.