NEC 690.7 PV string sizing & maximum system voltage
NEC 690.7 requires the maximum PV system voltage to be the sum of the module open-circuit voltages (Voc) corrected to the lowest expected ambient temperature — cold raises Voc — and it must not exceed the inverter's maximum DC input voltage.
The method
Corrected Voc per module = Voc × [1 + (Tmin − 25) × (β / 100)], where β is the temperature coefficient of Voc (%/°C, negative). Maximum system voltage = corrected Voc × modules in series. It must stay below the inverter's max DC voltage (commonly 500–600 V for residential string/hybrid inverters).
Max modules per string (Voc 40 V, β -0.28%/°C)
| Design low temp | 500 V inverter | 600 V inverter | 1000 V inverter |
|---|---|---|---|
| -10°C (14°F) | 11 | 13 | 22 |
| -20°C (-4°F) | 11 | 13 | 22 |
| -30°C (-22°F) | 10 | 12 | 21 |
Use the Extreme Annual Mean Minimum Design Dry Bulb Temperature for the site (ASHRAE) as Tmin. Related: 690.8 conductor & OCPD sizing.